20kv Load Break Switch Factories – FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric

Short Description:


Product Detail

Product Tags

Related Video

Feedback (2)

We are going to make every single effort for being excellent and excellent, and accelerate our ways for standing while in the rank of international top-grade and high-tech enterprises for Earthing System, Polymeric Insulator, 800mm Width Vcb Chassis Truck, We welcome new and old shoppers to make contact with us by telephone or mail us inquiries by mail for foreseeable future company associations and attaining mutual achievements.
20kv Load Break Switch Factories – FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric Detail:

General

FZN25-12DL/T630-20 indoor AC high voltage vacuum load switch is an indoor unit with three-phase AC of 50Hz,12KV rated voltage, applicable to industrial and mining enterprises’ power distribution stations and substations,etc. As the protection and control of electrical facilities, it is used for opening and closing load current, closed loop current, no-load transformer and cable charging current.

It matches an earthing switch with the ability to close short-circuit current. The operating mechanism can be divided into manual and electric type, which is convenient for realizing the three remote control requirements of the power system.

FZR25-12DL/T200-31.5 indoor AC high voltage vacuum load switch- fuse combination is an indoor unit with three-phase AC of 50Hz, 12KV rated voltage, applicable to industrial and mining enterprises’ power distribution stations and substations, etc.as short circuit protection and load confrol.

It matches an earthing switch with abiliy to close short-circuit current.The operating mechanism can be divided into manual and electric type,which is convenient for realizing the three remote control requirements of the power system.

Working Condition

●Alitude: 1000m.
●Ambient air temperature: Max.+40℃; Min.-25℃ (Allowed to storage and transportation at-30℃).
●Air relative humidity: Daily average is not greater than 95%, monthly average is not greater than 90%.
●Pollution level: II.
●Seismic intensity: Not more than 8 degree. No frequent and severe vibration.
●The surrounding air is not contaminated by corrosive or flammable gases, water vapor, etc.

Technical specification

No.

Ltem

Unit

Data

FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5

1

Rated voHoge

KV

12

2

Rated current

A

630

200

3

Rated frequency

HZ

50

4

Rated insulation level

I min power Lightning impulse withstand voltage

KV

Arc chamber between open contacts 30; To earth, phase to phase 42;lsolation between open contacts 48

Lightning impulse withstand voltage

KV

To earth, phase to phase 75; Isolation between open contact 85

5

Rated short-tine withstand current

KA

20

6

Rated short circuit duratton

S

4

7

Rated peak withstand current

KA

50

8

Rated active load breaking current

A

630

9

Rated closed-loop breaking current

A

630

10

Rated cable charging breaking current

A

10

11

Rated breaking no-lood transformer capacity

KVA

1600

12

Rated short-drcuit breaking current

KA

- 31.5

31.5

13

Rated transfer current

A

2000

14

Fuse type

SDLAJ-12、XPNTI-12

15

Impactor output energy

J

1+0.5

16

Rated short circuit closing currenl

KA

80 (Expected peak)

17

Earthing switch rated short-lime withstand current

KA

20

18

Earthing switch rated short drcurt duration

S

2

19

Earthing switch rated peak withstand current

KA

50

20

Auxiliary circuit rated voltage

V

≈220V、≈llOV

21

Mechanical life

Times

10000

 Outline overall and installing dimensions

 T200-315 Indoor AC High Voltage Vacuum Load Switch 001

 


Product detail pictures:

20kv Load Break Switch Factories –  FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric detail pictures

20kv Load Break Switch Factories –  FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric detail pictures

20kv Load Break Switch Factories –  FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric detail pictures

20kv Load Break Switch Factories –  FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric detail pictures

20kv Load Break Switch Factories –  FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric detail pictures


Related Product Guide:

Our business aims to operating faithfully, serving to all of our clients , and working in new technology and new machine continuously for 20kv Load Break Switch Factories – FZN25-12DL/T630-20 FZRN25-12DL/T200-31.5 Indoor AC High Voltage Vacuum Load Switch – Timetric , The product will supply to all over the world, such as: Lithuania, UAE, Bahamas, You can always find the products you need in our company! Welcome to inquire us about our product and anything we know and we can help in auto spare parts. We are looking forward to work with you for a win-win situation.
  • In our cooperated wholesalers, this company has the best quality and reasonable price, they are our first choice.
    5 Stars By Elsa from belarus - 2017.02.28 14:19
    Wide range, good quality, reasonable prices and good service, advanced equipment, excellent talents and continuously strengthened technology forces,a nice business partner.
    5 Stars By Martin Tesch from Myanmar - 2017.09.26 12:12
    Write your message here and send it to us