With our excellent administration, strong technical capability and strict excellent control method, we carry on to offer our clients with responsible good quality, reasonable costs and great companies. We intention at becoming considered one of your most responsible partners and earning your pleasure for Voltage Vacuum Circuit Breaker, SK-11 micro switch, Indoor Earthing, Our products are widely recognized and trusted by users and can meet continuously changing economic and social needs.
China Wholesale Indoor High Voltage Vacuum Breaker Factories – VSG-12 Indoor High Voltage Vacuum Circuit Breaker – Timetric Detail:

Summary:

VSG-12 Indoor High Voltage Vacuum Circuit Breaker(abbr.: circuit breaker) is three-phrase A.C. 50Hz indoor of power supply distribution equipped with the rated voltage 12 KV. This product is in accordance with GB1984-2003( high voltage A.C. circuit breaker),JB3855-1996 (3.6-4.5KV indoor A.C. high voltage circuit breaker), DL403-2000(technical conditions for ordering of 12-40.5KV high voltage vacuum circuit breaker) and IEC standard 62271-100:2001( high volage A.C. Circuit breaker). It can be used for protecting and controlling equipment in the grid equipment and the dynamic design of industrial and mining enterprise .It is suitable for switching load and frequent operation with different property and with the capability of many times operations of breaking short-circuit current.

Main Technical Parameters

Sequence number Name Unit Data
* Type  / □Handcart Type with Embedded Pole□Handcart Type with Insulated Cylinder

□Fixed type with Embedded Pole

□Fixed type with Insulated Cylinder

1 Rated voltage kV 12
2 Rated frequency Hz 50/60
3 Rated  insulating level 1min  power frequency withstand voltage kv 42
Rated lightning impulse withstand voltage kv 75
4 Rated current A 630 1250 1600 2000 2500 3150 4000
5 Rated short circuit breaking currentRated thermal stability current(effective value) kA 20
25 25
31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50
6 Rated short circuit making current(peak value)Rated dynamic current(peak value) kv 50
63 63
80 80 80 80 80
100 100 100 100 100
125
7 Rated short circuit current breaking times times 30,50
8 Rated thermal stability time s 4
9 Rated operating sequence times 0-0.3s-C0-180s-C
10 Mechanism life times 30000
11 The breaking current of single rated capacitance bank A 400
12 The breaking current of rated back to back capacitance bank S 4

Drawing 1A :

Rated current(A) 630 1250 1600
Rated short circuit breaking current(A) 20,25,31.5 20,31.5,40 31.5,40
The primary distance between phrases is 210mm.

Drawing 1B:

Rated current(A) 1600 2000 1600
Rated short circuit breaking current(A) 31.5,40
The primary distance between phrases is 275mm.

Drawing 1C:

Rated current(A) 2500 3150 4000
Rated short circuit breaking current(A) 31.5,40 40 40,50
The primary distance between phrases is 275mm.

Drawing 2A :

Rated current(A) 630 1250
Rated short circuit breaking current(A) 20,25,31.5 20,31.5,40
Φ35 Φ49
The mesh size between fixed and movable contacts should be not less than 15-25mm, the primary distance between phrases is 150mm.

Drawing 2B:

Rated current(A) 630 1250 1600
Rated short circuit breaking current(A) 20,25,31.5 20,31.5,40 31.5,40
Φ35 Φ49 Φ55
The mesh size between fixed and movable contacts should be not less than 15-25mm, the primary distance between phrases is 210mm.

Drawing 2C:

Rated current(A) 630 1250 1600
Rated short circuit breaking current(A) 20,25,31.5 20,31.5,40 31.5,40
Dimension of mating fixed contact(mm) Φ35 Φ49 Φ55
The mesh size between fixed and movable contacts should be not less than 15-25mm, the primary distance between phrases is 275mm.

Drawing 2D:

Rated current(A) 2500 3150 4000
Rated short circuit breaking current(A) 31.5,40 40 40,50
Dimension of mating fixed contact(mm) Φ109
The mesh size between fixed and movable contacts should be not less than 15-25mm, the primary distance between phrases is 275mm.

Ambient condition:

1. Altitude:≤1000m
2. Ambient temperature:-15°C~+40°C
3. Relative humidity: daiy average ≤95%, monhly average ≤90%
4. Earthquake intensity:≤ 8 degree
5.Applicable occasions should free from inflammables, explosives, corrosives and severe vibration.

VSG-12 Indoor High Voltage Vacuum Circuit Breaker

 

 


Product detail pictures:

China Wholesale Indoor High Voltage Vacuum Breaker Factories –  VSG-12 Indoor High Voltage Vacuum Circuit Breaker – Timetric detail pictures


Related Product Guide:

"Based on domestic market and expand overseas business" is our development strategy for China Wholesale Indoor High Voltage Vacuum Breaker Factories – VSG-12 Indoor High Voltage Vacuum Circuit Breaker – Timetric , The product will supply to all over the world, such as: Marseille, Myanmar, Sao Paulo, Till now, the goods list has been updated regularly and attracted clients from around the globe. Detailed facts is often obtained in our web-site and you'll be served with premium quality consultant service by our after-sale group. They are going to help you get comprehensive acknowledge about our products and make a satisfied negotiation. Company go to to our factory in Brazil is also welcome at any time. Hope to obtain your inquiries for any pleased co-operation.
  • Good quality, reasonable prices, rich variety and perfect after-sales service, it's nice!
    5 Stars By Candy from Thailand - 2018.02.04 14:13
    The supplier abide the theory of "quality the basic, trust the first and management the advanced" so that they can ensure a reliable product quality and stable customers.
    5 Stars By Lindsay from Los Angeles - 2018.07.26 16:51
    Write your message here and send it to us